    Everis BLQ6

    See Everis BLQ6 Products

    Everis™ BLQ6 quick disconnect couplings provide ultra-reliable, no-drip connections for thermal management to help protect valuable electronic systems. Designed specifically for blind mate liquid cooling applications, the Everis BLQ6 Series uses patent pending valve technology that eliminates drips and is specifically designed to withstand long-term connection. An optional accessory kit is available for panel mount connections.

    Assets & Downloads

    FeaturesBenefits
    Non-spill designDisconnect under pressure
    Redundant sealsExtra protection from contaminants and debris when couplers are connected
    Friction-free valveProvides reliability for extended periods of operation
    Rugged anodized aluminumAble to withstand long-term, ongoing and repeated use
    Axial engagement toleranceAllows full flow even when not fully engaged
    Optional panel mount kitEnables either the body, insert or both to be panel mounted

    Specifications & CV Value

    Operating Conditions (Fluid Transfer)

    Flow Coefficient: Cv ~ 2.2
    Pressure Range: Vacuum to 120 psi, 8.3 bar
    Operating Temperature: 0°F to 240°F (-17°C to 115°C)
    Storage/Shipping Temperature: -40°F to 240°F (-40°C to 115°C)

    Materials

    Material: Aluminum
    Material Finish: Anodized
    Seals: EPDM
    Mounting Options: Thread
    Valve: Polysulfone
    Valve spring : Stainless steel
    Compliance: RoHS, REACH

    Other

    Spillage: 0.03 cc per disconnect rated at 0 psi; 0.03 cc per disconnect rated at 120 psi
    Air Inclusion: 0.22 cc per connect
    Axial Mis-alignment: 1 mm max.
    See graphic below for the Panel Mount Kit (P/N BLQ6PMKIT).

    Cv Value

    Cv ~ 2.2 (Kv ~ 1.9)
    Cv values are based on gpm and psi, and Ipm and bar (shown in parentheses).